Owner`s manual
SCOTTY SS – INSTRUCTION MANUAL
Scotty SS Nov-05
22
- An ADD-ON unit must only be connected to an oil furnace, duct system and
chimney, which are in good operating condition.
- DO NOT interconnect an add-on with duct elbow less than 6” (152 mm) inside
radius.
- CAUTION: MAINTAIN COMBUSTION AIR TO FURNACES – AIR STARVATION
IS DANGEROUS.
2.10 Installers Final Checklist
DUCTWORK INSPECTION
1. Furnace ducted properly?
2. Proper duct clearances maintained?
FURNACE INSPECTION
1. DO NOT use firebrick in the furnace
2. Check settings on fan limit controls.
WIRING INSPECTION
1. Is main disconnecting switch within view?
2. Wiring cables protected from heat and not touching hot surfaces?
FLUE AND SMOKE PIPE INSPECTION
1. Flue inner size equivalent to 7” round or larger?
2. Separate entry and lower to flue for both solid-fuel and oil or gas smoke pipes?
3. Smoke pipe 24 gauge or better?
4. Smoke pipe secured by screws?
5. Draft regulator (if used) set at .05” w.c. maximum?
6. Clearances of smoke pipe 18” or better from combustible material?
Metal protection is recommended.
DEALER TO INSTRUCT HOMEOWNER
1. Keep area around unit clean.
2. Use DRY wood only. Hardwood is preferred.
3. Load carefully.
4. Load level no higher than center of door.
5. Remove ash regularly as directed.
6. Look for soot build up in smoke pipe.
7. Danger of flue fire if poor fuel or poor maintenance produces creosote buildup.
8. Operation of unit during power failure. (i.e. manual operation.)
9. When shutting down for extended periods, clean unit thoroughly.