Owner`s manual
6. Technician Settings
6.1 Adjust temperature limits for cool and heat, and offset for temperature reading.
• Set temperature to 50°F.
• Wait until the display
• Press and hold the SELECT button (5 sec.) – “COOL” and the temperature limit for
cooling will appear on display.
• Adjust the temperature limit for cooling (Limit Cool) using the “+” and “-“ buttons.
• Press the SELECT button again – “HEAT” and the temperature limit for heating will
appear on display.
• Adjust the temperature limit for heating (Limit Heat) using the “+” and “-“ buttons.
(Limit Heat should be higher than Limit Cool).
• Press the SELECT button again – the OFFSET temperature will appear on display (a
number between –6…+6). The offset is used for calibration of the measured temperature.
• Adjust the Offset for ambient temperature reading using the “+” and “-“ buttons.
• Press the SELECT button again to return to normal display.
6.2 Freeze Protection
• When the temperature drops below 45°F, the thermostat will turn on the Heat and Fan
outputs in order to protect the system from freezing.
• This function will be activated when the thermostat is either in On or Off position.
• The Display will alternate between ”AL” and “TEMP”
• The thermostat will return to normal mode when the temperature rises above 48°F.
10