6. Technician Settings
6.1 Adjust temperature limits for cool and heat, and offset for temperature reading.
Set temperature to 50°F.
Wait until the display
Press and hold the SELECT button (5 sec.) – “COOL” and the temperature limit for
cooling will appear on display.
Adjust the temperature limit for cooling (Limit Cool) using the “+” and “-“ buttons.
Press the SELECT button again – “HEAT” and the temperature limit for heating will
appear on display.
Adjust the temperature limit for heating (Limit Heat) using the “+” and “-“ buttons.
(Limit Heat should be higher than Limit Cool).
Press the SELECT button again – the OFFSET temperature will appear on display (a
number between –6…+6). The offset is used for calibration of the measured temperature.
Adjust the Offset for ambient temperature reading using the “+” and “-“ buttons.
Press the SELECT button again to return to normal display.
6.2 Freeze Protection
When the temperature drops below 45°F, the thermostat will turn on the Heat and Fan
outputs in order to protect the system from freezing.
This function will be activated when the thermostat is either in On or Off position.
The Display will alternate between ”AL” and “TEMP”
The thermostat will return to normal mode when the temperature rises above 48°F.