User's Manual
Table Of Contents
- Table of Contents
- List of Tables
- List of Figures
- Figure1.1 Typical SEL3022 and SEL5810 Virtual Serial Software Application 1.2
- Figure1.2 Encrypted Packet Stream 1.4
- Figure1.3 Typical Connections for the SEL3022 1.6
- Figure1.4 Typical Alarm Output Installation 1.8
- Figure2.1 SEL3022 Dimension Drawing 2.2
- Figure2.2 Windows Run Command 2.3
- Figure2.3 Product Unregistered Prompt 2.4
- Figure2.4 Select a Device Type to Create 2.7
- Figure2.5 Specify New Device Location 2.8
- Figure2.6 Opening Device 2.8
- Figure2.7 Identification Screen 2.9
- Figure2.8 Status: Device 2.10
- Figure2.9 Settings: Wireless 2.10
- Figure2.10 Settings: WEP Keys 2.11
- Figure2.11 Settings: User 2.11
- Figure2.12 Settings: Operator 2.12
- Figure2.13 Settings: Security Officer 2.12
- Figure2.14 Confirm Send Prompt 2.13
- Figure2.15 Send Operation Message 2.13
- Figure2.16 Select Items to Print 2.14
- Figure2.17 Print Window 2.14
- Figure3.1 Remotely Located Recloser Control 3.2
- Figure3.2 Job Done Example SEL-5809 Top Level View 3.3
- Figure3.3 Select a Wireless Session for DNP3 Job Done Example 3.4
- Figure3.4 Settings: DCE Port 3.4
- Figure3.5 Status: Virtual Serial Port With Connection Status Red 3.5
- Figure3.6 Communication Parameters Window in acSELerator 3.6
- Figure3.7 Status: Virtual Serial Port With Connection Status Green 3.6
- Figure3.8 Reading Settings Via the SEL3022 3.7
- Figure3.9 Monitoring SEL651R Meter Data Via the SEL3022 3.8
- Figure3.10 Status: Virtual Serial Port Connection Status Red 3.9
- Figure3.11 Specify Device to Export to SEL5810 Virtual Serial Software 3.10
- Figure3.12 Export Encrypted User Configuration File 3.10
- Figure3.13 Store Encrypted File 3.11
- Figure3.14 Password Prompt in SEL5810 Virtual Serial Software 3.12
- Figure3.15 Communication Parameters Window in acSELerator 3.13
- Figure3.16 Reading SER Report Via acSELerator 3.14
- FigureB.1 PC to SEL3022 Connection B.2
- FigureB.2 SEL3022 and SEL-5809 Connection Parameters B.2
- FigureB.3 SEL5809 Settings Software Connection Method B.3
- FigureB.4 SEL-5809 Opening Connection B.3
- FigureB.5 Status: Device Window B.4
- FigureB.6 Confirmation Prompt B.4
- FigureB.7 Send Operation Prompt B.4
- FigureB.8 Configuring Serial Port Settings in the Terminal Software B.5
- FigureB.9 Send File Prompt B.6
- FigureB.10 Sending Confirmation Window B.6
- FigureB.11 Terminal Invalid Firmware Error Message B.7
- FigureB.12 Terminal Valid Firmware Message B.7
- FigureC.1 Two Independent Layers of Cryptographic Security Protect the SEL3022 Wireless Operato...
- FigureC.2 Operation of the HMAC SHA-1 Keyed Hash Authentication Function C.9
- FigureC.3 Operation of the AES Encryption Function C.10
- FigureC.4 SEL3022 Security Application Overview C.11
- FigureC.5 Wireless Interface Session Authentication Dialog C.15
- Preface
- Introduction & Specifications
- Installation
- Job Done Example
- Settings and Commands
- Testing and Troubleshooting
- Firmware and Manual Versions
- Firmware Upgrade Instructions
- Wireless Operator Interface Security
- Introduction
- Wireless Interface Security Overview
- IEEE 802.11 WEP Security
- The SEL Security Application
- Certificates
- Glossary
SEL-3022 Transceiver Instruction Manual Date Code 20050615
Testing and Troubleshooting
Testing Philosophy
5.2
Cryptographic Manual—Do Not Copy
Testing Philosophy
SEL-3022 testing can be divided into three categories: acceptance, commissioning, and
maintenance testing. The categories are differentiated both by when they take place in
the life cycle of the transceiver and by test complexity. The paragraphs below describe
when you should perform each type of test, the goals of testing at that time, and the
functions that you need to test at each point.
This information is intended as a guideline for testing an SEL-3022.
Acceptance Testing
Perform acceptance testing when qualifying an SEL-3022 for use in a serial
communication system that requires data encryption.
Goals of Acceptance Testing
➤ Ensure that the SEL-3022 meets published critical performance
specifications.
➤ Ensure that the SEL-3022 meets the requirements of the intended
application.
➤ Improve your familiarity with SEL-3022 capabilities.
What to Test
Acceptance test all setting parameters critical to your intended application.
SEL performs detailed acceptance testing on all SEL-3022 models and versions. Any
SEL-3022 we ship meets published specifications. It is important for you to perform
acceptance testing on an SEL-3022 if you are unfamiliar with SEL-3022 operating
theory or settings. Such testing helps you ensure that SEL-3022 settings are correct for
your application.
Commissioning Testing
Perform commissioning testing when installing a new SEL-3022 Serial Encrypting
Transceiver.
Goals of Commissioning Testing
➤ Ensure that power connections are correct.
➤ Ensure that the Alarm Output connection is correct.