User's Manual

RADIORANGER Instruction Manual Date Code 20070301
SEL-8310 Remote Fault Reader Operation
Operation
3.14
correspond to speaker volume and LED intensity. The SEL-8310 will exit the HMI
Adjust Mode five seconds after the last button press or after pressing and holding both
the
{Scan} and {Next} buttons simultaneously for one second. Following HMI Adjust
Mode termination, the SEL-8310 reenters Normal Mode. The same data displayed
prior to entering HMI Adjust Mode will be available.
While the device is in the HMI Adjust Mode, the
{Scan} button cycles through the four
possible volume levels. The volume level is represented by solid yellow
WIRELESS
INTERFACE ID
LEDs in a bar chart style from left to right. A single LED bar represents
no volume; four LED bars represent maximum volume, which is the default. Each
{Scan} button press selects the next highest volume level until it reaches the maximum
volume level. At that point, pressing the
{Scan} button again takes the unit back to the
lowest volume level. When the SEL-8310 exits the HMI Adjust Mode, any adjustments
made to the volume level are updated in the Flash memory and are active when the
Normal Mode resumes.
While the device is in the HMI Adjust Mode, the
{Next} button cycles through three
possible LED brightness levels. The solid yellow LEDs that represent the volume level
also adjust their brightness in response to presses of the
{Next} button. Each {Next}
button press selects the next highest brightness level until the maximum level is
reached. At that point, pressing the
{Next} button again selects the lowest brightness
level. When the device exits the HMI Adjust Mode, any adjustments made to the
brightness level are updated in the Flash memory and are active when the Normal
Mode resumes.