User's Manual

Table Of Contents
SEL-3031 Instruction Manual Date Code 20091009
Settings and Commands
Commands
4.24
STATUS Command
Use STA to display the status report, as shown in Table 4.21.
Refer to Section 5: Performance Monitoring, Testing, and Troubleshooting for self-test
thresholds and corrective actions, as well as information on hardware configuration
conflict resolution. Figure 4.11 shows the device response to the STA command.
=>>STA <Enter>
RADIO 1 Date: 10/10/2009 Time: 16:44:00
STATION_A Time Source: Internal
Serial Number: 2009275250
FID=SEL-3031-R100-V0-Z001001-D20091009 CID=25D052CF
RFID=SEL-3031-R100-V0-D20091009
BFID=SLBT-3031-R100-V0-Z000000-D20091009
Part number 30310W01XXX
PROTOCOLS
PORT 1 PORT 2 PORT 3
STANDARD MODBUS MB8
SELF TEST RESULTS
FLASH SDRAM RADIO RTC SEC
OK OK OK OK ABSENT
Device Enabled
Figure 4.11 Device Response to the STATUS Command
Table 4.22 shows the status report definitions and message formats for each test.
Table 4.21 STA Command (Device Self-Test Status)
Command Description Access Level
STA n Displays the device self-test information n times
(n = 1–32767). Defaults to 1 if n is not specified.
1
STA C Reboots the device and clears self-test warning and
failure status results.
2
Table 4.22 STA Command Report (Sheet 1 of 2)
Status Report
Designator
Definition Message Format
FID Firmware identifier string Text Data
RFID FPGA Firmware identifier string Text Data
BFID SELBOOT Firmware identifier string Text Data
Part Number Part Number of the SEL-3031 Text Data
PORT 1, 2, 3 Protocol setting for port 1, 2, and 3 STANDARD, MB8, MODBUS