User's Manual

Table Of Contents
Date Code 20091009 SEL-3031 Instruction Manual
Settings and Commands
Commands
4.17
ASCII Commands
The SEL-3031 includes ASCII commands and settings to properly set the SEL-3031.
ACSELERATOR QuickSet software provides a user-friendly interface to set the
SEL-3031, but either interface can be used to set the product.
DATE Command
Use the DATE command to view and set the date, as shown in Table 4 .8 .
The device can overwrite the date entered with other time sources, such as IRIG. Enter
DATE to set the internal clock date. Separate the month, day, and year parameters with
slashes. Set the year in four-digit format (for dates 2000–2099).
IDENTIFICATION Command
The ID command extracts device identification codes, as shown in Table 4.9. The ID
command is only available as a compressed (comma-delimited) command.
IRIG Command
Use the IRI command to read the demodulated IRIG-B time code at the management
port or IRIG-B input, and to force immediate synchronization of the internal clock with
the IRIG-B signal (see Tabl e 4.10). If an IRIG-B signal is present at serial Port 2, the
device will automatically synchronize the internal clock with the IRIG-B signal in a
time period not exceeding one minute. It is not necessary to issue the IRI command for
this automatic synchronization. If you are testing the device and do not want to wait for
Ta b le 4. 8 DAT E Com m an d
Command Description Access Level
DAT Displays the internal clock date. 1
DAT date Sets the internal clock date (DATE_F set to MDY,
YMD, or DMY).
1
Ta b le 4.9 ID C o m m a n d
Command Description Access Level
ID Returns a list of device identification codes, as shown
below:
=ID <Enter>
"FID=SEL-3031-R100-V0-Z001001-D20091009","08D2"
"BFID=SLBT-3031-X307-V0-Z000000-D20091009","0974"
"CID=2B957901","0330"
"DEVID=RADIO 1","03D9"
"DEVCODE=72","0310"
"PARTNO=30310W01XXX","0538"
"CONFIG=00000000","03E3"
"SPECIAL=0","02DE"
1