User's Manual

Table Of Contents
SEL-3031 Instruction Manual Date Code 20091009
Introduction and Specifications
Specifications
1.8
Receiver
Sensitivity: –97 dBm
Bit Error Rate
(BER): <10
–6
at –97 dBm
Distance: 20 miles, line of sight
Error Detection: 32-bit CRC (MB8 mode)
Power Supply
Rated Supply Voltage
Wall-Mount
Model: 12/24 Vdc
Low-Voltage
Model: 24/48 Vdc
High-Voltage
Model:
125/250 Vdc
110/240 Vac, 50/60 Hz
Input Voltage Range
Wall-Mount
Model: 9–30 Vdc
Low-Voltage
Model: 18–60 Vdc
High-Voltage
Model: 85–275 Vdc; 85–264 Vac
Power Consumption
Wall Mount: < 5 W
Rack Mount: < 7 W
Type Tests
Communications Equipment Tests
IEEE 1613-2003
Environmental Tests
Enclosure
Protection: IEC 60529:2001
Vibration
Resistance:
IEC 60255-21-1:1988
Class 1 Endurance,
Class 2 Response
IEC 60255-21-3:1993
Class 2
Shock
Resistance:
IEC 60255-21-2:1988
Class 1 shock withstand,
bump,
Class 2 shock response
Cold: IEC 60068-2-1:2007
–40°C, 16 hours
Damp Heat,
Cyclic:
IEC 60068-2-30:2005
25–55°C, 6 cycles, 95%
relative humidity
Dry Heat: IEC 60068-2-2:2007
+85°C, 16 hours
Dielectric Strength and Impulse Tests
Dielectric
(HiPot):
IEC 60255-5:2000
IEEE C37.90–2005
Impulse: IEC 60255-5:2000
0.5 J, 5 kV
RFI and Interference Tests
EMC Immunity
Standard: IEEE 1613, Class 2
Electrostatic
Discharge:
IEC 61000-4-2:2008
Severity Level 4
8 kV contact discharge
15 kV air discharge
IEEE C37.90.3–2001
Severity Level 4
8 kV contact discharge
15 kV air discharge
Radiated RF
Immunity:
IEC 61000-4-3:2008
10 V/m
IEEE C37.90.2–2004
35 V/m
Fast Transient,
Burst
Immunity:
IEC 61000-4-4:2004
4 kV @ 2.5 kHz, and 5.0
kHz for communications
ports, power supply,
alarm contacts
Surge Withstand
Capability
Immunity:
IEC 60255-22-1:2007
2.5 kV common-mode,
1 kV differential-mode
IEEE C37.90.1–2002
2.5 kV oscillatory, 4 kV
fast transient for
communications ports,
power supply, alarm
contacts
Conducted RF
Immunity:
IEC 61000-4-6:2008
10 Vrms
Digital Radio
Telephone RF
Immunity:
ENV 50204-1995
Severity Level 10 V/m at
900 MHz and 1.89 GHz