User's Manual
6
SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317
Application Examples
Figure 5 Recloser Communication With Fault Transmitters
Each SEL-FT50 monitors line current and instantly transmits a wireless signal
when an overcurrent (fault) condition occurs. The companion SEL-FR12
receives and aggregates fault data from as many as 12 SEL-FT50 Fault
Transmitters. Upon detecting a fault indication signal, the SEL-FR12
communicates the fault information to the host SEL-651R recloser control, or
other SEL protective relay, by using M
IRRORED BITS communications.
The SEL-FT50/SEL-FR12 system allows the protective relay or recloser
control to make intelligent decisions by using high-speed fault information
from remote locations.
Improve Fuse
Coordination
In a radial distribution system, there are two main schemes that control fuse
coordination: fuse-saving and fuse-blowing (also called trip-saving). Each of
these schemes has shortcomings that you can address with the
SEL-FT50/SEL-FR12 system.
Figure 6 gives a representation of a typical time-overcurrent coordination
graph.
R
Wireless
SEL-FT50
SEL-FT50
SEL-FT50
SEL-FT50
SEL-FR12
SEL-651R-2