User's Manual

28
SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317
Appendix B: Two Branch Application
With these settings, Branch B operates using a fuse-blowing scheme where the
fuse clears faults on the branch, while Branch A operates separately, tripping
much faster because the protection does not wait for a fuse-coordination delay.
Table 12 Settings for the SEL-FR12
Network ID BAUD RX_ADD TX_ADD Trio 1 Distance Trio 2 Distance Trio 3 Distance Trio 4 Distance
3—(0010) 38400 1 2 > 300 m (1000 ft) > 300 m (1000 ft) > 300 m (1000 ft) > 300 m (1000 ft)
Table 13 SEL-651R Settings
PROTO SPEED TXID RXID
MB8A or MB8B 38400 1 2
Table 14 SEL-651R Transmit MIRRORED BITS Settings
TMB1A TMB2A TMB3A TMB4A TMB5A TMB6A TMB7A TMB8A Comments
0 0 0 0 0 0 0 TRGTR The TARGET RESET pushbutton of
the SEL-651R resets the latched
FAULT LEDs of the SEL-FR12.