Owner`s manual

7
STW-JZ / IW I&O Manual
IM101229
RL: 12A- BA
RD: DEC 2010
TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES*
FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - refer to Table 1 for values
*The clearance to combustible materials represents the minimum distance that must be main-
tained between the heater and a nearby surface. The stated clearance to combustibles
represents a surface temperature of 90F° (50C°) above room temperature. .
NOTE that in the above table the clearances are measured from the reflector
.
It is the installer’s responsibility to ensure that building materials with a low heat toler-
NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED: USE AN INDELIBLE MARKER TO
ENTER VALUES ‘H’, ‘S’, ‘F’, & ‘B’ ON THE SIGN.
POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.
See next page for details.
F
D
B
A
S
S
C
Suspended at an
angle up to 45°
Suspended
horizontally
C
FLOOR
H
T
H
Maximum
Stack Height
H = T- C
‘T’ is meas-
ured on site,
FLOOR
T
Maximum
Stack Height
H = T- C
‘T’ is meas-
ured on site,
MODEL
SUSPENDED AT AN ANGLE
UP TO 45 DEGREES
SUSPENDED
HORIZONTALLY
D
inches (cm)
B
inches (cm)
F
inches (cm)
C
inches (cm)
A
inches (cm)
S
inches (cm)
C
inches (cm)
STW-JZ/IW 200
13 (33)
6 (15.2)
74 (188) 70 (178)
14 (36) 44 (112)
76 (193)
STW-JZ/IW 175
12 (31)
6 (15.2)
72 (183) 68 (172)
13 (33) 42 (107)
74 (188)
STW-JZ/IW 155
5.5 (14)
1 (2.5)
44 (112) 64 (163)
3.5 (9) 19 (48)
64 (163)
STW-JZ/IW 130
4.5 (11)
1 (2.5) 35 (89)
60 (152)
3.3 (9) 11 (28)
60 (152)
STW-JZ/IW 110 3.5 (9) 1 (2.5) 26 (66)
54 (137)
2 (5) 10 (25)
54 (137)
STW-JZ/IW 80 3 (8) 1 (2.5) 23 (59) 38 (97) 1.75 (5) 6 (15) 38 (97)
STW-JZ/IW 60 2.5 (6) 1 (2.5) 17 (43) 34 (86) 1.5 (4) 5.5 (14) 34 (86)
STW-JZ/IW 45 2.75 (7) 1 (2.5) 24 (61) 32 (81) 2.25 (6) 7 (18) 32 (81)