Owner`s manual

39
STW-JZ / IW I&O Manual
IM101229
RL: 12A- BA
RD: DEC 2010
 CHECK 120V SUPPLY TO RELAY SWITCH
 IF ELECTRICAL SUPPLY PROBLEM …. MAKE RE-
QUIRED REPAIR TO RESTORE 120V
 CHECK FOR 120V FROM RELAY SWITCH
 IF “NO” SWITCHING IS OCURRING......REPLACE
THE RELAY SWITCH
SET THERMOSTAT TO CALL FOR HEAT
APPLY 120 VOLTS - GREEN LIGHT IS ON
 CHECK IF 120 VOLTS PRESENT AT BLOWER
 IF “YES”.....REPLACE DEFECTIVE BLOWER
COMBUSTION AIR BLOWER STARTS
A.P.S. HAS CLOSED (B.F.S. IS CLOSED)
24 VOLTS PRESENT AT DSI CONTROL.
AMBER LIGHT IS ON
 CHECK FOR OBSTRUCTION IN THE AIR INTAKE
AND FLUE
 CHECK TUBING TO SWITCHES IS CONNECTED
AND NOT BLOCKED OR KINKED
 CHECK IF AIR PROVING SWITCH IS CLOSING
WHEN BLOWER IS RUNNING
 CHECK AIR PRESSURE WITH MANOMETER
 REPLACE ANY DEFECTIVE SWITCH
 CHECK DSI CONTROL FUSE FOR CONTINUITY
 VISIBLY CHECK IF IGNITER IS SHORTING OUT
 CHECK GROUND WIRING
 REMOVE AND INSPECT IGNITER AND LEAD
 CHECK BOOT OF THE IGNITION CABLE FOR SIGNS
OF MELTING OR OVERHEATING
 IF “YES” ... TAKE PROTECTIVE ACTION TO SHIELD
CABLE AND BOOT FROM EXCESSIVE TEMPERA-
TURE; REPLACE ANY DEFECTIVE COMPONENT
 CHECK CERAMIC INSULATOR AND CAP
 CHECK SPARK GAP SETTING IS 3/16” (ADJUST BY
MOVING THE GROUND PRONG ONLY
)
 PERFORM IGNITION LEAD TEST (See SPARK IGNI-
TION CIRCUIT INSTRUCTIONS—Section 22)
 GOOD SPARK.....REPLACE IGNITER
 NO SPARK/OR WEAK.....REPLACE CONTROL
SPARK IGNITER / SENSOR
24V TO GAS VALVE - RED LIGHT IS ON
CONTINUED
SEQUENCE OF EVENTS
21. TROUBLESHOOTING GUIDE
NO
YES
WARNING
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician
YES
YES
NO
NO
 CHECK 24V SUPPLY TO RELAY SWITCH
NO