Owner`s manual
38 
SET(U)-F / ITT(U)-F Manual 
IM091221 
RD: FEB 2014 
RL: 8B 
MAIN BURNER LIGHTS 
SYSTEM RUNS UNTIL CALL FOR HEAT 
ENDS 
CALL FOR HEAT ENDS: 
SYSTEM SHUTS OFF 
TROUBLESHOOTING ENDS 
SEE S87J DSI CHECK 
 CHECK FOR STRONG SPARK AT IGNITER........ 
 (SEE PREVIOUS PAGE). 
 CHECK FOR 24 VAC ACROSS GAS VALVE. 
 CHECK OUTPUT VOLTAGE FROM CONTROL TER-
MINALS TO GAS VALVE.....IF NO VOLTAGE RE-
PLACE CONTROL. 
 CHECK ELECTRICAL WIRING, AND VOLTAGE BE-
TWEEN IGNITION CONTROL AND GAS VALVE. 
 IF OK, REPLACE GAS VALVE. 
NOTE: IF IGNITION CONTROLS GOES INTO A 
LOCKOUT, INTERRUPT POWER AND RESTART.
 CHECK CONTINUITY OF SENSOR CABLE AND 
GROUND WIRE AS A POOR GROUND COULD RE-
SULT IN ERRATIC BEHAVIOUR AND NUISANCE 
SHUTDOWNS EVEN THOUGH OPERATION IS NOR-
MAL AT THE TIME OF CHECKOUT. 
 CHECK FOR EXCESSIVE HEAT AT SENSOR INSU-
LATOR AS TEMPERATURES ABOVE 1000°F(538°C) 
CAUSES SHORT TO GROUND. 
 CHECK FLAME SIGNAL IN SERIES WITH THE 
GROUND AND MODULE FOR A MINIMUM 1.5UA. 
 IF SIGNAL IS LOWER CHANGE IGNITER. 
 IF CHECKS ARE OK.....REPLACE CONTROL. 
 CHECK TEMPERATURE CONTROLLER. 
 CHECK FOR FAULTY WIRING, REMOVE GAS 
VALVE LEAD AT CONTROL , 
 IF VALVE CLOSES, RECHECK THE TEMPERATURE 
CONTROLLER AND WIRING. 
 IF VALVE STAYS OPEN....REPLACE GAS VALVE 
SPARK STOPS WHEN BURNER LIGHTS 
CONTROL IS NOT SENSING FLAME WITHIN THE 
21 SECOND TFI AND IS STILL TRYING TO LIGHT
 CHECK CONTINUITY OF SENSOR CABLE AND 
GROUND WIRE 
 CHECK BURNER FLAME IS COVERING SENSOR. 
 CHECK FLAME SIGNAL IN SERIES WITH THE 
GROUND AND MODULE FOR 1.5UA MINIMUM. 
 IF SIGNAL IS LOWER CHANGE IGNITER. 
 IF CHECKS ARE OK.......REPLACE CONTROL. 
NO 
YES 
NO 
YES 
YES 
YES 
NO 
NO 