SPARK IGNITER ADJUSTMENT 
Use the following diagram to check the Igniter gap. If the gap is incorrect all adjustments 
should be made to the GROUND PRONG/PIN ONLY! DO NOT BEND THE IGNITER 
PRONG!!!! 
3/16” 
1/4” 
3/16” 1/4” 
IF 
this manual is in 
8.5” x 11” “booklet” format 
(pages folded in half) 
then use these bars 
IF this manual is printed  
8.5” x 11” “full page” format 
use these bars 
OR 
ADJUST 
SERVICE CHECKS  
Flame current passes through the flame from 
the sensor to ground. The minimum flame cur-
rent necessary to keep the system from lock-
out is 0.7 microamps. To measure flame cur-
rent, connect an analog DC microammeter to 
the FC- FC+ terminals per figure at right. 
Meter should read 0.7 µA or higher. If the me-
ter reads below “0” on scale, meter leads are 
reversed. Disconnect power and reconnect 
meter leads for proper polarity. 
FC- FC+ 
Use Microamp 
scale 
Multipurpose Meter 