Owner`s manual

26
P40U / P40U-I &O Manual
IM101220
RD: DEC 2011
RL: 1A - BA
Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The heater includes
a 24V/120V relay switch . Maximum power draw for internal 24V burner components is 21VA.
The heater must be electrically grounded in accordance with the National Electrical Code.
ANSI / NFPA 70 or current Canadian Electrical code CSA C22.1.
A maximum night set-back of 9°F (5°C) is recommended for optimum economy and comfort.
To maintain satisfactory comfort levels do not turn off the heating system over night/weekends.
Maximum Power Draw = 21VA
17A. MODELS P40U-P, P40U-W WIRING DIAGRAM: 24V OR 120 VOLT THERMOSTAT
SINGLE HEATER PER THERMOSTAT
Models P40U, -I …. Previous Page
Multiple Heaters/Thermostat … Page 27