Technical data

infraSchwank D / calorSchwank D - shape U
14
Version 004 infra_calor D shape U Australia 43/13 Technical specification subject to change
Technical data
for single and two-stage regulation
Gas
15U 20U 30U 40U
Natural gas
Gas consumption [MJ/h]
1)
single state
Gas consumption [MJ/h]
2-stage/modulating max./min.
Propane
Gas consumption [MJ/h]
2)
2-stage/modulating max./min.
Gas consumption [MJ/h]
2-stage/modulating max./min.
Weight infra / calor [kg] 54 / 68 75 / 95 92 / 119 130 / 171
of air/exhaust flue [mm]
Electrical consumption [W]
Electrical protection
Gas connection (male)
R
3
/
4
Electrical supply
Ignition / Control
CE-Identification
AGA Certification no.
113.5 152.6
58.7 - 43.8 74.4 - 56.0 113.5 - 86.1 152.6 - 117.4
155.8
by automatic controller system
CE - 0085 BO 0037
230 V/ 50 Hz ~
Spark ignition and ionisation control
75.9 - 57.2 115.9 - 87.9 155.8 - 119.9
58.7 74,4
R½“
7652
infraSchwank D / calorSchwank D
Ø 100
IP 20
104
59.9 - 44.7
59.9 75.9 115.9
1) H
i,B
= 37.8 MJ/m
3
/ 2) H
i,B
= 95.8 MJ/m
3
Tab 4: Technical data infraSchwank D / calorSchwank D
1) H
i,B
= 37.8 MJ/ m
3
/ 2) H
i,B
= 95.8 MJ/m
3
*) IA= inlet angle plate
Tab 5: Function parts burner unit infraSchwank D / calorSchwank D
Gas
15U 20U 30U 40U
Natural gas
Burner nozzle [mm] 3.75 4.10 5.35 6.25
1)
Fan air restrictor plate D 15 D 20 D 30 D 40
Air baffle plate D 15 D 20 D 30 + spin D 40 U
Burner baffle plate Ø 50 Ø 50 Ø 65 /
Nozzle pressure [kPa]
1-stage 0.87 0.87 0.87 0.87
2-stage
0.87 / 0.6 0.87 / 0.6 0.87 / 0.6 0.87 / 0.6
Start step pressure [kPa] 0.4 0.4 0.4 0.3
MIN MIN MIN MIN
Propane
Burner nozzle [mm] 2.30 2.50 3.15 3.60
2
)
Fan air restrictor plate D 15 D 20 D 30 D 40
Air baffle plate D 15 D 20 D 30 + spin D 40 U
Burner baffle plate Ø 50 Ø 50 Ø 65 Ø 65
Nozzle pressure [kPa]
1-stage 2.4 2.4 2.4 2.4
2-stage
2.4 / 1.4 2.4 / 1.4 2.4 / 1.4 2.4 / 1.4
Start step pressure [kPa] 1.2 1.2 1.2 1.2
MAX MAX MAX MAX
infraSchwank D / calorSchwank D
Start step adjustment [°]
Start step adjustment [°]