Operating instructions

infraSchwank D / calorSchwank D - shape U
13
Version 005 infra_calor D shape U Australia 42/14 Technical specification subject to change
Flexible exhaust system infraSchwank D / calorSchwank D 15-40U (wall terminal)
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal by
compression strongly together!
All joints inside the building tighten
securely with clamp fittings!
The 90° elbow at the sucking fan side is to
mount with the opening on the top.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 80mm
- double-wall exhaust pipe +
wall terminal: 0mm
System certification tube heater
infraSchwank D / calorSchwank D with
exhaust line system
Future ew CE 0432–CPD219983 /
Future ew-flex CE 0432–CPD-219952 /
Future dw CE 0432-CPD-219996
(Schräder)
Fig. 11: Position of control points 15 – 40U (wall terminal), version stainless steel