Operating instructions
infraSchwank D / calorSchwank D - shape U
11
Version 005 infra_calor D shape U Australia 42/14 Technical specification subject to change
Flexible exhaust system infraSchwank D / calorSchwank D 15-40U (wall terminal)
- version aluminium -
The stainless flexible pipe (exhaust
line) must be installed uncut for the
heater 40U. Make sure that there is no
sink in the pipe.
All socket connections on the
exhaust and air line must be locked
by means of self-tapping screws.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.
The 90° elbow at the sucking fan side is
to mount with the opening on the top.
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 40mm
- double-wall exhaust pipe + wall
terminal: 0mm
System certification tube heater
infraSchwank D / calorSchwank D
with exhaust line system
CE 0432-CPD-217915, System 0.2 / 0.5
(Muelink&Grol)
Fig 9: Position of control points 15 – 40U (wall terminal), version aluminium
control points
condensate collector
exhaust gas:
stainless flexible pipe
combustion ai
r
:
15 - 20U: aluminium flexible pipe
30 - 40U: stainless flexible pipe
wall terminal