9.6 SUGGESTED MOUNTING DISTANCE FOR COMFORT**
*Reflector with venturi must be in upper position
** These mounting distances are suggested and are subject to on sight conditions. If in doubt, please
contact your Schwank distributor.
Page 10
Since most installations will differ in many de-
tails, these instructions are general. Sound judg-
ment must be exercised and careful supervision is
essential to assure the installation will be made in
the best manner possible for trouble-free opera-
tion and at minimal cost. All systems must be
done in accordance with acceptable practices, lo-
cal codes, and applicable standards.
This heater is suitable for reflector mounting an-
gles up to 30
0
degrees along the short axis
Improper angle mounting can result in overheat-
ing of controls and combustible materials.
IMPORTANT: For either horizontal or angle
mounting, the long axis of the heater must be
level. Use only non-combustible mounting
hardware.
NOTE: It is the responsibility of the installer to
insure that the chosen suspension system will sup-
port at least 200 lbs.
MOUNTING HEIGHTS:
ecoSchwank 6 10 13 18 26
Distance to floor 12’ 16’ 20’ 24’ 28’
Maximum heater spacing 16’ 22’ 28’ 34’ 39’
Maximum distance between heater rows 25’ 30’ 40’ 50’ 70’
HORIZONTAL suggested mounting distance for comfort.*
ecoSchwank 6 10 13 18 26
Distance to floor 12’ 13’ 17’ 20’ 22’
Maximum heater spacing 16’ 22’ 28’ 34’ 39’
Maximum distance between heater rows 25’ 30’ 40’ 50’ 70’
ANGLE suggested mounting distance for comfort.*