Owner's manual

22
P40R-F I&O Manual
IM120801
RD: MAY 2014
RL: 3A
FIGURE 11: LOCATION OF HORIZONTAL (SIDE WALL) VENT TERMINAL
Clearance required: Canada
1
USA
2
Above grade, veranda, porch, deck, balcony 12” (30 cm) 12” (30 cm)
To a window or door that may be opened 12” (30 cm) 9” (23 cm)
To a permanently closed window ** **
Below a ventilated soffit within 2 ft horizontal from
center of terminal
12” (30 cm) 9” (23 cm)
Below an unventilated soffit 3” (7.6 cm) 3” (7.6 cm)
To an outside corner 12” (30 cm) 12” (30 cm)
To an inside corner 12” (30 cm) 12” (30 cm)
To each side of centerline extended above a
meter/regulator assembly
3 ft (91 cm) within 15 ft (4.5 m)
height above meter/regulator
**
To a service regulator vent outlet 3 ft (91 cm) **
To non-mechanical air supply inlet or combustion
air inlet to other appliance
12” (30 cm) 9” (23 cm)
To mechanical air supply inlet 6 ft (1.83 m)
3 ft (91 cm) above
if within 10 ft (3 m)
horizontally
Above sidewalk or paved drive on public property 7 ft (2.13 m) † **
A
B
C
D
E
F
G
H
I
J
K
L
M
Under veranda, porch, deck, balcony 12” (30 cm) ‡ **
See Table footnotes previous page
TABLE 3