Manual

46
SPW-JZ, STW-JZ(2) / IWP, IW(2) I&O Manual
IM101229
RL: 13A
RD: MAY 2014
26. INPUT & TUBE KIT(S) REQUIRED
BEFORE INSTALATION:
ENSURE you have the CORRECT TUBE KIT(s) for the BURNER INPUT
USA - Stainless Steel Flexible Gas Connector
130,000 or less:
JL-0771-XX - 1/2”x24”
155,000 or more:
JL-0771-YY - 3/4”x36”
FLEXIBLE GAS CONNECTOR (Included in Burner Kit) - MUST INSTALL - see Section 13
CANADA - Type 1 Hose Gas Connector
130,000 or less:
JL-0771-RC - 1/2”x30”
155,000 or more:
JL-0771-RB - 3/4”x36”
CAPACITY
INPUT
(Btuh)
TUBE
LENGTH
SPW-JZ / IWP & STW-JZ / IW
ALUMINIZED STEEL TUBE KITS
(individual cartons)
STW-JZ2 / IW2
STAINLESS STEEL TUBE KITS
(individual cartons)
Tube Kit 1 # Tube Kit 2 # Tube Kit 1 # Tube Kit 2 #
45,000 20'
TW-1420-JZ - TW-1420-JZ2 -
60,000 20'
TW-1420-JZ - - -
30'
TW-1430-JZ - TW-1430-JZ2 -
80,000 20'
TW-1420-JZ - - -
30'
TW-1430-JZ - TW-1430-JZ2 -
40'
TW-1040-JZ - TW-1040-JZ2 -
110,000 30'
TW-1430-JZ - - -
40'
TW-1040-JZ - TW-1040-JZ2 -
50'
TW-F030-JZ TW-0020-JZ TW-F030-JZ2 TW-0020-JZ2
130,000 30'
TW-1430-JZ - - -
40'
TW-1040-JZ - TW-1040-JZ2 -
50'
TW-F030-JZ TW-0020-JZ TW-F030-JZ2 TW-0020-JZ2
150,000 40'
TW-1040-JZ - - -
50'
TW-F030-JZ TW-0020-JZ TW-F030-JZ2 TW-0020-JZ2
60'
TW-F030-JZ TW-0030-JZ TW-F030-JZ2 TW-0030-JZ2
175,000 50'
TW-1030-JZ TW-0020-JZ - -
60'
TW-1030-JZ TW-0030-JZ TW-1030-JZ2 TW-0030-JZ2
70'
TW-1030-JZ TW-0040-JZ TW-1030-JZ2 TW-0040-JZ2
200,000 50'
TW-1030-JZ TW-0020-JZ - -
60'
TW-1030-JZ TW-0030-JZ TW-1030-JZ2 TW-0030-JZ2
70'
TW-1030-JZ TW-0040-JZ TW-1030-JZ2 TW-0040-JZ2