Instruction Manual
2100 / IO 100 Manual 
IM110107 
 RD: MAY 2014 
R.L. 4A 
37 
MAIN BURNER LIGHTS 
SPARK STOPS WHEN 
BURNER LIT. 
DOES FLAME REMAIN 
STABLE AFTER THE 
SPARK CYCLE IS COM-
PLETE. (NO FLAME FAIL) 
*CHECK FOR CORRECT MANIFOLD GAS PRESSURE 
*CHECK FOR OBSTRUCTION IN GAS SUPPLY OR 
ORIFICE (INSECTS, SPIDERS COCOONS ETC.)  
CHECK SENSOR FLAME SIGNAL WITH METER FOR 
0.7µA MINIMUM STEADY READING. 
IF READING IS LOW CHECK GAS PRESSURE 
IF OK .....CHANGE SENSOR. 
CHECK FOR CONTINUITY OR SENSOR CABLE AND 
GROUND WIRE. 
CHECK THAT BURNER FLAME COVERS ALL ELEC-
TRODES. IF CHECKS ARE OKAY, REPLACE CONTROL 
MODULE. 
NOTE: IF GROUND IS POOR OR ERRATIC, SHUT-
DOWN MAY OCCUR OCCASIONALLY EVEN THOUGH 
OPERATION IAPPEARS NORMAL AT THE TIME. 
CHECK FOR PROPER TEMPERATURE CONTROLLER 
OPERATION. 
CHECK SENSOR FLAME SIGNAL WITH METER FOR 
0.7µA MINIMUM STEADY READING.(REPEAT ABOVE) 
CALL FOR HEAT ENDS; 
SYSTEM SHUTS OFF 
TROUBLE SHOOTING ENDS 
NOTE: IF CONTROL GOES INTO LOCKOUT, THE SYSTEM CAN BE 
RESET BY INTERRUPTING THE POWER SOURCE 
NO 
YES 
YES 
NO 
YES 
NO 
NO 
CHECK FLAME SIGNAL WITH METER FOR 0.7µA. 
IF READING IS LOW CHECK GAS PRESSURE, IF OK 
CHANGE SENSOR. 
CHECK FOR CONTINUITY OR SENSOR CABLE AND 
GROUND WIRE. 
CHECK THAT BURNER FLAME COVERS ALL ELEC-
TRODES. 
IF CHECKS ARE OKAY, REPLACE CONTROL MODULE. 
SYSTEM RUNS UNTIL 
CALL FOR HEAT ENDS 
CHECK AND ADJUST TEMPERATURE CONTROLLER 
SETTING AND CHECK CONTROLLER CONNECTIONS 
CHECK FOR PINCHED WIRING. 
REMOVE VALVE LEAD AT CONTROL IF VALVE 
CLOSES, RECHECK TEMPERATURE CONTROLLER 
AND WIRING; 
IF VALVE DOES NOT CLOSE REPLACE GAS VALVE. 
YES 
NO 