Datasheet
4
3-Phase AC Filters / DC Filters
FMAC
www.schurter.com /PG80
EMC Products
Technical data to the filter components
Rated Current
@ Ta 40°C (75°C)
Characteristic Rated Voltage [VAC] L [mH] C1 [μF] C2 [μF] C3 [nF] C4 [nF] C5 [μF] C6 [μF] R1 [MΩ] R2 [MΩ] R3 [MΩ] R4 [MΩ]
6 (6) Excellent attenuation - 10 1.0 - 100 10 2.2 - - - 1 1
8 (5) Excellent attenuation 480 10 1.0 - 100 10 2.2 - - - 1 1
16 (10) Excellent attenuation 480 6 1.0 - 100 10 2.2 - - - 1 1
16 (Pending) High voltage filter 520 6 1.5 - 50 11 1.5 - 2 1 1 2
16 (10) Excellent attenuation - 6 1.0 - 100 10 2.2 - - - 1 1
25 (15) Excellent attenuation - 3 4.4 1 10 47 4.4 1 2.2 1 1 2.2
25 (14) High attenuation - 2.4 4.4 1 10 47 4.4 1 2.2 - 1 2
25 (Pending) High voltage filter 520 3 3 1.1 50 11 3 1.1 2 1 1 2
36 (20) High attenuation - 1.5 4.4 1 10 47 4.4 1 2.2 - 1 2
36 (Pending) High voltage filter 520 2 3 1.1 50 11 3 1.1 2 1 1 2
50 (32) Excellent attenuation - 1 4.4 1 10 100 4.4 1 2.2 1 1 2.2
50 (30) High attenuation - 1 4.4 1 10 100 4.4 1 2.2 - 1 2
50 (Pending) High voltage filter 520 1 3 1.1 50 11 3 1.1 2 1 1 2
64 (37) High attenuation - 0.6 4.4 1 10 100 4.4 1 2.2 - 1 2
80 (45) Excellent attenuation - 1 6.6 1 47 100 6.6 1 2.2 1 1 2.2
80 (Pending) High voltage filter 520 1 4.5 1.1 50 50 4.5 1.1 2 1 1 2
64 (37) Excellent attenuation 480 0.6 4.4 1 10 100 4.4 1 2.2 1 1 2.2
64 (Pending) High voltage filter 520 0.6 3 1.1 50 11 3 1.1 2 1 1 2
110 (70) Excellent attenuation - 0.7 6.6 1 47 100 6.6 1 2.2 1 1 2.2
110 (Pending) High voltage filter 520 0.7 4.5 1.1 50 50 4.5 1.1 2 1 1 2
180 (Pending) Excellent attenuation - 0.4 6.6 1 47 100 6.6 1 2.2 1 1 2.2
180 (Pending) High voltage filter 520 0.4 4.5 1.1 50 50 4.5 1.1 2 1 1 2
250 (Pending) Excellent attenuation - 0.3 11 1 100 100 11 1 2.2 0.5 0.5 2.2
250 (Pending) High voltage filter 520 0.3 7.5 1.1 50 50 7.5 1.1 2 1 1 2
340 (Pending) Excellent attenuation - 0.2 11 1 100 100 22 1 2.2 0.33 0.33 2.2
340 (Pending) High voltage filter 520 0.2 7.5 1.1 50 50 15 1.1 2 1 1 2
450 (Pending) Excellent attenuation - 0.2 11 1 100 100 22 1 2.2 0.33 0.33 2.2
550 (Pending) Excellent attenuation - 0.2 11 1 100 100 22 1 2.2 0.33 0.33 2.2
1100 (Pending) High voltage filter 520 0.12 11 1.1 50 - 22 1.1 2 0.5 0.25 2
Diagrams
1)
1) Line