Datasheet
7
3-Phase AC Filters / DC Filters
FMAC ECO
https://www.schurter.com /PG80
EMC Products
All Variants
Bemessungs-
strom @ Tu 40°C
(75°C) [A]
Characteristic Rated Voltage [VAC] Tripped Po
-
wer Dissipa-
tion [W]
Leakage
Current [mA]
@ 440V,
Contact Resi
-
stance [mΩ]
Weight
[kg]
Screw clamps
[mm2] 2)
Housings Order Number
16 High attenuation 480 6 8.9 7.6 1 kg 4 1C FMAC-091C-1610
█
25 High attenuation 480 8 8.9 4.1 1 kg 4 1C FMAC-091C-2510
36 High attenuation 480 10 8.9 2.5 1.3 kg 6 1D-6 FMAC-091D-3610
█
50 High attenuation 480 13 10.2 1.7 1.7 kg 10 1D-10 FMAC-091D-5010
55 High attenuation 480 14 10.2 1.5 1.7 kg 10 1D-10 FMAC-091D-5510
64 High attenuation 480 17 10.2 1.4 2 kg 16 1E FMAC-091E-6410
█
110 High attenuation 480 28 11.8 0.8 5.8 kg 50 1G FMAC-091G-H110
150 High attenuation 480 40 11.8 0.6 7 kg 50 1G FMAC-091G-H210
80 High attenuation 480 22 11.1 1.1 5.1 kg 25 1T FMAC-091T-8010
64 High attenuation 480 17 10.2 1.4 2 kg 16 SF FMAC-3FSF-6410
█
█ Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) Nominal leakage current acc. to IEC60950 - 5.2.5. under normal operating conditions. Note: worst case leakage current acc. to IEC60950 - Annex G4 (situation with two inter-
rupted lines) can be much higher.
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the general product information www.schurter.com/
emc_info
Packaging unit
1 Pcs
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
15.06.2018