Owner's manual
Minimum Off: 010 s
Fan Control – Head Pressure Control
Setp: 190 Band: 030
Vspeed: ENABLE / DISABLE
Min Freq: 030 Max: 060
Condenser Fan Config
VFD minimum: 000 Hz
VFD Maximum: 065 Hz
Factory Settings
Temperature Unit:
0
F
Pressure Units: PSI Changing this parameter will not display correct reading in BAR
Password Maintenance
Factory Pass: 0177
Supervisor setup
Ident: 001
Baud: 1200
Protocol: n/a
Unit Configuration
Evap Sensors: No
Voltage Monitor: Yes
Misc Settings
Tiem Betw Comps: 010 s
Screen Saver Delay: 005 min
Serial No
Change Serial No on the Chiller
Hi Temp Alarm
Enable: Yes
ALARM HISTORY
THIS DISPLAYS THE LAST 20 ALARM FAULT CODES.
DATE AND TIME
Date / Time Settings:
THIS SETS THE CURRENT DATE AND TIME
SENSOR CALIBRATION
Head Pressure #1
Current: Current head pressure reading
Off set: 00 psi offset value
Min: 000 Psi Max: 415
Head Pressure #2
Current: Current head pressure reading
Off set: 00 psi offset value
Min: 000 Psi Max: 415
Discharge Temp