Manual
To Condenser
Chiller Discharge Line
Ball Valve
8' of rise or more requires Oil trap at base of the rise
25' or more of rise requires a trap at
the base and one along the mid point
of the rise
(Ex. 40' of rise requires one trap at
base and one trap at 20')
Discharge Line Detail
Short Radius Elbow
All Voltages
SCHREIBER
ENGINEERING
12111 E. Park St.
Cerritos CA 90703
562-926-3855
562-926-0969- FAX
www.trueton.com
All Models
MODEL
FILENAME
PHILIPS CONDENSER
INTERCONNECT.VSD
DRAWN BY
JEFF JOHNSON
DATE
5/1/2002
VOLTAGE
DRAWING NO.
DESCRIPTION
REMOTE CONDENSER INSTALLATION DETAILS
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
Liquid
Connections
Hot Gas
Connections
1 2 1 2
Condenser End View
All connections are "
1 2 1 2
Chiller End View
All connections are "
All refrigeration piping valves shown
are supplied by Schreiber.
Hot gas shutoff on chiller side is provide by
compressor discharge service valve.
Liquid
Connections
Hot Gas
Connections
Liquid Lines- 5/8"
Hot Gas Lines- "
Liquid Lines- 5/8"
Schrader Valves
(field installed)