Manual
allows the chiller to run, but water must be added immediately. Since the reservoir is open to the
atmosphere, a small amount of water may be lost due to evaporation. The local weather conditions
will dictate how often the reservoir should be topped off. If water needs to be added more than once a
month, there is a possibility of a leak in the system.
Flow Switch
There is a ow switch on each piping loop to protect the chilled water system. When the switch is
open (no ow) the pump on that loop will not run. If the ow switch is open on the GCHE loop, it will
also lock out the compressors to keep from freezing the evaporators. On pump startup, there is a
short time delay 15-25 seconds, to allow ow to be established before generating an error. When
running, there is a another time delay of 5-10 seconds to allow for ow disruptions caused by a
changed in valve position or bubbles in the system.
Backow Kit
Since the chilled water reservoir is vented to the atmosphere, water in pipes above the water level of
the reservoir will ow back and overow the reservoir when the pumps are shut off. To prevent this, a
backow kit consisting of a solenoid valve on the return line on each loop , and a check valve on the
GCHE loop is provided. The solenoid valve is a normally closed valve that is energizes whenever the
pump contactor is energized.
The backow kit also keeps the entire piping loop full of water during shut down. In some cases
(including startup) the pump will start when the pipe is not full. Since the ow switch is on the return
line, the pump may alarm on a ow error on pumped startup, because the time required to ll the
pipes and trigger the ow switch was longer than the time delay at pump startup. The alarm can be
reset, or the ow time delay temporarily increased to allow for pipe lling.
COMPRESSOR/EVAPORATOR SYSTEM
Refer to the following:_