Datasheet

Datasheet Rev. FG1
Issued 2006/07
www.tycoelectronics.com
www.schrackrelays.com
Dimensions are in mm unless
otherwise specified and are
shown for reference purposes
only.
Product specification
according to IEC 61810-1.
Product data, technical para-
meters, test conditions and
processing information
only to be used together
with the 'Definitions' at
schrackrelays.com in the
‘Schrack’ section.
Specifications subject to
change.
General Purpose Relays
1
Slim PCB Relay SNR
I
1 pole 6 A, 1 CO or 1 NO contact
I
Only 5 mm wide
I
Sensitive coil 170 mW
I
4 kV coil-contact, 6 / 8 mm clearance/creepage, NO version
with 8 / 8 mm clearance/creepage on request
I
Reinforced insulation (protection class II)
I
Allows high function-/packing density
I
Cadmium-free contacts, AgNi 90/10 for AC-loads
I
RoHS compliant (Directive 2002/95/EC) as per product date
code 0404
Applications: centralized and decentralized heating control,
extremely narrow interface elements, interface technology,
timers, PLC's, I/O modules, I/O-ports
F0140-C
Approvals
V REG.-Nr. 6666, Z E214024
Technical data of approved types on request
Contact data
Contact configuration 1CO or 1NO
Contact set single contact
Type of interruption micro disconnection
Rated current 6 A
Rated voltage / max.switching voltage AC 240/400 VAC
Maximum breaking capacity AC 1500 VA
Limiting making capacity, max 4 s, duty factor 10% 10 A
Contact material AgSnO
2
AgSnO
2
AgNi90/10
gold plated
Minimum contact load 100mA, 12V 50mW 100mA, 12V
Mechanical endurance 10x10
6
cycles
Rated frequency of operation with / without load 6 /1200 min
-1
Contact ratings
Type Load Cycles
V23092-*****-A302 3(1,5)A, 250VAC, 85°C, 1mm mounting distance,
6 cycles / min, EN60730-1 100x10
3
V23092-*****-A302 5(1,5)A, 250VAC, 85°C, 0,5mm mounting
-A802 distance, 6 cycles / min, EN60730-1 10x10
3
V23092- Pilot Duty R300 28 VDC, 85°C, 6000 cycles, UL508
V23092- Pilot Duty B300 240 VAC, 85°C, 6000 cycles, UL508
Coil data
Rated coil voltage range DC coil 5...60 VDC
Coil power DC coil typ. 170 mW
Operative range 2
Coil versions, DC-coil
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
VDC VDC VDC Ohm mW
005 5 3.5 0.25 147+10% 170
012 12 8.4 0.6 848+10% 170
024 24 16.8 1.2 3390+10% 170
048 48 33.6 2.4 10600+15% 217
All figures are given for coil without preenergization, at ambient temperature +23°C
Other coil voltages on request

Summary of content (3 pages)