Installation Manual
3
solar.schneider-electric.com
Conext™ MiniPower Distribution Panel Installation Guide
865-1013-01
975-0735-01-01 Revision B
05-2015
Remove the XW/XW+ AC access panel.
Replace the DC terminal flat and split washers then the bolts on the Positive (+)
(shown) and Negative (–) DC terminals in the correct order as shown below.
Replace the DC terminal caps (provided with the XW/XW+) on the
DC terminals to cover them.
terminal surface
DC bus bar conductor
flat washer
split washer
bolt
Torque bolts to
180 in-lbf (15 ft-lb).
G
Wiring the Mini PDP
Complete all internal AC and DC wiring. See wiring diagrams on pages 4 and 5.
• Connecting AC wires to the inverter
• Connecting Generator AC wires to a fourth AC breaker and
to the Inverter
• Connecting PV Inverter AC wires to a fourth AC breaker and
to the Bypass terminals
• Connecting DC cables from the PV breaker to the MPPT 60 150
and to the PV array
For detailed communication and analog wiring
instructions, see the Conext XW/XW+
Inverter/Charger Installation Guide
Complete all communication and analog wiring (for example, Xanbus, AC sync,
AUX, and BTS). Ensure all communication and analog wires are routed through
the routing trays and barriers as shown.
Replace the front faceplate of the Mini PDP.
Replace the 8 screws previously set aside (step E1) to secure the faceplate.
Replace the door of the Mini PDP, if previously removed.
Replace the XW/XW+ AC access panel from step E1.
Installation complete. Follow XW/XW+ Installation Guide instructions to
complete unit comissioning.
XW+ unit (shown)
Remove the communication cable barriers for easy routing of communication wiring.
Replace the barriers after wiring.
Run communication wiring only
through cable routing trays that
shield them from EMI interference
coming from the power cables.
two pieces