Product Manual

Configuration via SCP
4–30 975-0636-01-01 Rev E
When installing a multiple unit system, every setting on the Multi Unit Config
menu (except for Dev Name) must be configured for each Conext SW in the
system. The settings should be configured in the following order: Dev Number
then Invtr Mode.
AC In setting The Conext SW accepts only a single AC source - either from the grid or from a
generator. In a power system where the Conext SW is solely connected to the
grid and an AGS is neither present nor required, the AC In setting can be either
Gen1 or Grid1. Therefore, the default value of Gen1 need not be changed.
In a situation where the AC source is a generator and the AGS is being used to
start the generator to produce AC power, the AC In setting must be set to Gen1.
Therefore, the default value of Gen1 must remain unchanged.
In a power system where the two AC sources are available but only one AC
source can be used, an external transfer switch becomes necessary. When an
external transfer switch is used and an AGS (with a B+ signal connection) is also
present, change the AC In setting to Grid1.
Setting the Device Name
The Dev Name setting allows you to customize the name of the Conext SW as it is
displayed on other screens and menus.
The available characters are:
A to Z
a to z
0 to 9
•space
AC In For identifying the type
of AC source when two
power sources are
available and an AGS is
also present.
Gen1 Gen1, Grid1
Battery For identifying batteries
only.
HouseBatt1 HouseBatt1...
HouseBatt5
a.Applies to all Conext SW models.
Table 4-18 Multi Unit Menu Description and Values
a
Item Description Default Range
NOTE: Increasing the number of characters in a device name may cause other
text on the same line to run off the edge of the screen. Device names should be
limited to 10 characters or less.
ConextSWEUROwnersGuide.book Page 30 Thursday, July 23, 2015 3:32 PM