Product Manual

Configuration via SCP
4–28 975-0636-01-01 Rev E
Additionally, with these scenario settings, the Conext SW would enter load
shaving within the configured time and also only if the battery has been charged
from an MPPT charge controller in Float (including Absorption) for 2 hours.
Enhanced AC Support Setting
Self-consumption The goal of the enhanced AC support (EnhancedACSup) feature is to make sure
that the power system self-consumes the power it harvests from a PV array. It
does this by keeping the battery bank charged up and ready to supply power to
the loads.
When EnhancedACSup is enabled, the Conext SW supports local loads by
converting excess capacity from external DC sources connected to its battery
bank. An example of an external DC source is the Conext MPPT solar charge
controller like the MPPT 80 600.
To use the Enhanced AC Support feature:
1. Enable AC support mode. AC support mode is enabled by default. Check
only to see if it is enabled. If not, enable it.
2. Enable enhanced AC support.
NOTE: In the absence of an MPPT charge controller, charger block stop and
start settings must be set at the same times as the load shaving stop and start
settings. Otherwise, charging may start even during load shaving.
CSW4024E 00: AC Support
AC Supp Mode
AC Supp Volts
Load Shave
Load Shave Amps
[Enabled]
]
[Disabled]
[24A]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
[26.0V
Go to Advanced Settings -> AC Support -> AC Supp Mode
CSW4024E 00: Adv Fea
StoreInvState
AcCouple
EnhancedAcSup
PLSDelay
[Disabled]
[Disabled]
[Enabled]
[Enabled]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go back to Advanced Settings -> Adv Features -> EnhancedAcSup
Press Enter, then select Enabled using the up
and down arrow buttons. Press Enter.
ConextSWEUROwnersGuide.book Page 28 Thursday, July 23, 2015 3:32 PM