Product Manual

Configuring Advanced Settings
975-0636-01-01 Rev E 4–27
To use the Load Shaving feature:
1. Enable load shaving.
2. Set the load shaving amps.
3. Set the load shaving start and stop times.
4. Enable the grid-interactive delay feature.
In this scenario, load shaving is only entered and exited as programmed within
the time window (from 6 AM to 9 PM).
CSW4024E 00: AC Support
AC Supp Mode
AC Supp Volts
Load Shave
Load Shave Amps
[Disabled]
[26.0V]
[Enabled]
[24A]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go to Advanced Settings -> AC Support -> Load Shave
Press Enter, then select Enabled using the up and down arrow
buttons. Press Enter.
From AC Support -> Load Shave Amps
Press Enter, then select a value of 10 using
the up and down arrow buttons. Press Enter.
CSW4024E 00: AC Support
AC Supp Mode
AC Supp Voltsp
Load Shave
Load Shave Amps
[Enabled]
[Disabled]
[Enabled]
[10A]
From AC Support -> LoadShaveStart
Press Enter, then a time of 9:00 PM using the
up and down arrow buttons. Press Enter.
Press Enter, then a time of 6:00 AM using the
up and down arrow buttons. Press Enter.
From AC Support -> LoadShaveStop
CSW4024E 00: AC Support
LoadShaveStart
LoadShaveStop
AC Supp on Soc
AC Supp Start Soc
[6:00 AM]
[9:00 PM]
[Disabled]
[80%]
CSW4024E 00: Adv Fea
StoreInvState
AcCouple
EnhancedAcSup
PLSDelay
[Disabled]
[Disabled]
[Disabled]
[Enabled]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go back to Advanced Settings -> Adv Features -> PLSDelay
Press Enter, then select Enabled using the up and down arrow
buttons. Press Enter.
ConextSWEUROwnersGuide.book Page 27 Thursday, July 23, 2015 3:32 PM