Product Manual
Configuration via SCP
4–22 975-0636-01-01 Rev E
NOTE: If a warning is received indicating that a setting is not accepted by the
SCP, gradually increase the value of the setting until the SCP accepts it. This
type of warning means that an internal minimum threshold value is being crossed
and therefore the setting cannot be saved.
AC Settings
The AC Settings menu configures the voltage and frequency limits for AC In.
These are the limits at which the Conext SW considers input voltage qualified—
that is, suitable for charging batteries or powering loads. If the input voltage is
not qualified according to these settings, the Conext SW transfers from using AC
input to inverting.
Bulk Voltage Sets the bulk voltage for a LithiumIon battery type.
Max Bulk
Current
Sets the maximum bulk current for a LithiumIon battery type.
Absorb
Voltage
Sets the absorption voltage for a LithiumIon battery type.
Max Absorb
Current
Sets the maximum absorption current for a LithiumIon battery
type.
Float
Voltage
Sets the float voltage for a LithiumIon battery type.
Max Float
Current
Sets the maximum float current for a LithiumIon battery type.
DisChgImax Sets the maximum current discharge in percentage.
DisChgImax
Timer
Sets the maximum current discharge timer.
Table 4-14 Custom Battery Settings Menu Description
Item Description
Figure 4-8 AC Settings Menu Screen
CSW4024E 00: AC
ACIn Breaker
ACIn Lo Volt
ACIn Hi Volt
ACIn Lo Freq
ACIn Hi Freq
AC Qualify Time
[30.0A]
[170.0V]
[270.0V]
[45Hz]
[55Hz]
[5sec]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
[*170.0V] [170.0V] to [220.0V]
[*30A] [5A] to [30A]
[*270.0V] [240.0V] to [270.0V]
[*45Hz] [40Hz] to [48Hz]
[*55Hz] [52Hz] to [68Hz]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
ConextSWEUROwnersGuide.book Page 22 Thursday, July 23, 2015 3:32 PM