Product Manual

Inverter/Charger Operation using the System Control Panel (SCP)
975-0636-01-01 Rev E 3–17
NOTE: Meters and View Device Info are not operational settings rather they are
informational. Basic and Advanced Settings are covered in another section of the
guide.
To change an operational setting:
1. From the device Setup menu screen, use the up or down arrow buttons to
highlight any operational setting you wish to change.
2. Press Enter then use the up or down arrow buttons to move between
selections. For example, the inverter setting can be changed to either
Enabled or Disabled.
3. Press Enter to confirm the selection.
4. Press Exit (twice) to go back to the System Status menu screen.
To clear fault detections/warnings:
1. From the device Setup menu screen, use the up or down arrow buttons to
highlight Clear Faults/Warnings.
2. Press Enter to clear the highlighted selection.
Figure 3-8 Conext SW Setup Menu Operational Settings
CSW4024E 00: Setup
Meters
Inverter
Search Mode
Charger
Force Chg State
Equalize
Mode
Clear Faults/Warnings
View Device Info
Basic Settings
[Enabled]
[Disabled]
[Enabled]
[Bulk]
[Disabled]
[Operating]
[*Enabled] [Disabled]
[*Enabled] [Disabled]
[*Enabled] [Disabled]
[*Bulk] [Float] [NoFloat]
[*Enabled] [Disabled]
[*Operating] [Standby]
ConextSWEUROwnersGuide.book Page 17 Thursday, July 23, 2015 3:32 PM