Installation Manual
Specifications
2–2 975-0637-01-01 Rev E
This guide for use by qualified personnel only
Inverter Specifications
NOTE: All inverter specifications are at nominal conditions: ambient temperature
of 25 °C, 230 VAC, 50 Hz input, unless otherwise specified
AC Output SW 2524 230 SW 4024 230 SW 4048 230
Output waveform true sine wave true sine wave true sine wave
Output power (AC)
- Maximum continuous
- 30 minutes
- 5-second surge
3000 W
3300 W
a
5000 W
b
a.Duty cycle 3300 W for 30 minutes, 0 W for 45 minutes
b.Duty cycle 5000 W for 5 seconds, 3000 W for 300 seconds.
3400 W
4000 W
c
7000 W
d
c.Duty cycle 4000 W for 30 minutes, 0 W for 45 minutes.
d.Duty cycle 7000 W for 5 seconds, 3400 W for 300 seconds.
3800 W
e
4400 W
e
7000 W
e.Only when NoLoadVD is enabled.
Maximum continuous
allowable (in pass-thru)
30 A 30 A 30 A
Inverter continuous output current
13 A 16 A 16 A
Inverter peak output current 24.3 A 42 A 42 A
AC OUTPUT connection
Single-Phase
(L, N,
)
Single-Phase
(L, N,
)
Single-Phase
(L, N,
)
Peak efficiency 91.5% 92% 94%
Operating voltage range 216–232 VAC 216–232 VAC 219–240 VAC
Nominal voltage 230 VAC 230 VAC 240 VAC
Operating frequency range selectable
50 or 60 Hz
selectable
50 or 60 Hz
selectable
50 or 60 Hz
Default output frequency 50 Hz 50 Hz 50 Hz
DC Input SW 2524 230 SW 4024 230 SW 4048 230
Voltage range 20–34 VDC 20–34 VDC 40–64 VDC
Maximum short-circuit current 10,000A 10,000A 10,000A
Maximum continuous power
voltage range
22–27 VDC 22–27 VDC 46–48 VDC
Maximum allowable current 250 A 250 A 250 A
No-load power draw (Inverter On)
24 W29 W27 W
Low battery voltage shutdown
cut-off (other values selectable)
21.0 V
(default)
21.0 V
(default)
42.0 V
(default)
High battery voltage shutdown
cut-off (other values selectable)
33.0 V
(default)
33.0 V
(default)
62.0 V
(default)