Step 3: Connecting the AC Input and AC Output Wires
General AC Wiring Considerations
AC and DC Wiring Separation Do not mix AC and DC wiring in the same
conduit or panel. Consult the applicable installation code for details.
AC Knockouts There are two dual 1" and 3/4" trade-size knockouts on the side
panel and another two on the bottom panel for AC wiring. Use the same trade
size of strain relief as the trade size of the knockout(s) you are using.
AC Wiring Terminals The AC wiring terminals accept cables of a specific size.
See “AC Wiring” on page 1–12 for required sizes.
DANGER
ELECTRICAL SHOCK AND FIRE HAZARD
• Make sure all AC and DC wiring being connected to the inverter/charger is
disconnected (physically or by opening and locking out all relevant
disconnecting means) from all electrical sources before handling.
• All wiring must be done in accordance with local and national electrical
wiring codes.
• Replace the wiring box cover after wiring.
Failure to follow these instructions will result in death or serious injury.
NOTICE
EQUIPMENT DAMAGE
Do not remove or loosen factory installed wiring in the inverter’s terminal block.
The terminal block is split into INPUT and OUTPUT sections. Damage may
occur if the unit is wired incorrectly.
Failure to follow these instructions can damage the inverter/charger.