C
Knockout Dimensions
D
Installing Wall Brackets
44.6 mm
Inner: 2" trade (62.7 mm)
Outer: 3" trade (90.0 mm)
Inner: 1/2" trade (22.2 mm or PG16)
Outer: 3/4" trade (28.0 mm)
Cable Management Anchors
Fits 8 mm wide cable ties
Ground Bus Bar
DC Negative Bus Bar
Ground Bus Bar
AC Neutral Bus Bar
Raceway for routing
Xanbus, AC Sync, Aux,
and BTS cables
between inverters
When removing your choice of knockouts, ensure no debris remains inside the chassis. Insert
appropriately-sized conduit bushings.
Side Knockouts
Holes for mounting
Conext MPPT 60 150
solar charge controllers
Knockouts for installing
optional surge arrestors
1//2" trade (22.2 mm or PG16)
Remove the left or right adjustable sideplate
adjacent to the Conext XW+ to route wiring from
the Conduit Box (interior screw not shown)
Remove the raceway knockout
to route wiring from the Conduit
Box
EQUIPMENT DAMAGE
Do not drill, cut or punch holes into the Conduit Box, XW+ chassis, or Power Distribution
Panel. Use only the knockouts provided for conduit entry.
Failure to follow these instructions can result in damage to equipment.
NOTICE
Top Knockouts
Knockouts for installing
optional surge arrestors
1//2" trade (22.2 mm or PG16)
Inner: 2" trade (62.7 mm)
Outer: 2 1/2" trade (75.4 mm)
Bottom Knockouts
Inner: 3/4" trade (28.2 mm or PG21)
Outer: 1" trade (35.0 mm)
7x
Inner: 3/4" trade (28.2 mm or PG21)
Outer: 1" trade (35.0 mm)
4x
3x
Inner: 28.2 mm
Outer: 35.0 mm
2x
Inner: 3/4" trade (28.2 mm or PG21)
Outer: 1" trade (35.0 mm)
4x
Inner: 2" trade (62.7 mm)
Outer: 2 1/2" trade (75.4 mm)
Inner: 3/4" trade (28.2 mm or PG21)
Outer: 1" trade (35.0 mm)
6x
1//2" trade (22.2 mm or PG16)
Back Knockouts
(interior view)
Inner: 1/2" trade (22.2 mm or PG16)
Outer: 3/4" trade (28.0 mm)
2x
Install the mounting plates
The Conext XW+ and PDP use identical interlocking mounting plates.
Use a level to ensure the first mounting plate for the XW+ unit is level. Install adjacent
mounting plates for additional XW+ units and PDP without additional measuring or
leveling.
If necessary, enhance wall surface with 3/4" plywood panel spanning at least three
wall studs.
Choose recommended mounting hardware
Wall mount fasteners are not included with the PDP. Use the type of fastener appropri-
ate for the wall material:
Structure Required Fastener Screws per Plate
Wood studs 16" on-center (O.C.) 1/4" Ø × 3 1/2" long lag screw 4
Wood studs 16" O.C. 1/4" Ø × 1" long wood screw 6
(3/4" min. plywood panel required)
Steel studs 16" O.C. 1/4" Ø self-drilling screw 4
(18 gauge min.)
16”
4 ½”
2”
6”
1 ¾”
17”
6
7
8
9
3
16
2 ¼”
¾”
1
2x4 wall stud, 16" centers
wall board
plywood (optional)