Installation Guide

2
Copyright © 2014 Schneider Electric. All Rights Reserved.
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
www.SESolar.com
Conext System Control Panel Installation Guide
865-1050-01
D
Connecting Xanbus Cables
SHORT CIRCUIT OF NETWORK COMPONENTS
This network is not an ethernet system. Only connect Xanbus-enabled devices to other Xanbus-enabled devices.
Do not attempt to connect Xanbus-enabled devices to other networks or systems.
Ethernet crossover cables are not compatible with the Xanbus system. Use Category 5 (CAT 5 or CAT 5e) cables
to connect Xanbus-enabled devices.
Do not install network terminators in an AC Sync port.
Failure to follow these instructions can result in damage to equipment.
NOTICE
XANBUS SHOCK HAZARD
Xanbus cables in contact with DC or AC power can transmit an electric shock.
Do not route the Xanbus cables in the same conduit or panel as the AC and DC power cabling.
Failure to follow these instructions can result in death or serious injury.
WARNING
Xanbus cables are connected to the SCP at the time the SCP is mounted.
Connecting Xanbus cables to the SCP
1. Connect the Xanbus cable (or two Xanbus cables if the SCP is located between two
Xanbus-enabled devices) to a Xanbus network input in the SCP.
2. Route and connect the cable(s) to the nearest Xanbus-enabled device(s).
3. For additional devices, continue connecting cable as described above.
4. Ensure the factory-supplied male network terminators are inserted into the empty inputs
in the Xanbus-enabled devices at the beginning and end of the network. When the
network is completely connected, there should be no empty network inputs in any
Xanbus-enabled device.
IGNITION AND FIRE HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do not install this product in locations that
require ignition-protected equipment. This includes any confined space containing vented batteries, or flammable
chemicals such as, natural gas (NG), liquid petroleum gas (LPG) or gasoline (Benzine/Petrol).
Do not install in a confined space with machinery powered by flammable chemicals, or storage tanks, fittings, or
other connections between components of fuel or flammable chemical systems.
Do not install the SCP near readily flammable materials such as cloth, paper, straw, or plastic sheeting. Keep
flammable materials a minimum distance of 600 cm (24 in.) from the top surface and 30 cm (12 in.) from either
side surface and the front of the SCP.
Failure to follow these instructions can result in death or serious injury.
WARNING
For detailed instructions on installing the Xanbus network, see the Conext System
Control Panel Owners Guide.
E
Wall Mounting the System Control Panel
Flush mount the SCP using the mounting plate
1. Using a jigsaw and the supplied template sticker as a
guide, cut out the hole for the mounting plate. The mount-
ing plate fastens to walls up to 19 mm thick.
2. Route the Xanbus cable(s) inside the wall and through the
opening.
4. Secure the mounting plate. Tighten the two screws to rotate
the tabs to the horizontal position and pull the tabs tight
against the inner surface of the wall. Be careful not to
overtighten the screws and damage the wall.
5. Connect the Xanbus cable(s) (and terminator if necessary) to either network input on the
back of the SCP. Connect a network terminator to the SCP if it is the last device at the end
of a daisy chain network layout.
Important: To ensure communication signal quality, the
network must be terminated at each end with a terminator.
6. Place the unit into the mounting plate
and secure it with four #6 screws.
7. Peel off the protective plastic coating
covering the screen and indicator light.
Flush mount the SCP with no mounting plate
Surface mount the SCP using the mounting bracket
1. Using the template sticker as a guide, mark the location for the area to be cut out.
2. Pilot-drill the mounting holes (if necessary), and use a jigsaw to cut out the hole in
which the SCP will be inserted.
3. Route the Xanbus cable(s) from other Xanbus-enabled devices inside the wall and
through the opening.
4. Connect the Xanbus cables to either network input on the back of the SCP. Connect a
network terminator to the SCP if it is the last device at the end of a daisy chain
network layout.
5. Place the unit in the opening and secure it with four #6 screws. Peel off the protective
plastic coating covering the screen and indicator light.
1. Using the supplied template sticker as a guide, mark the locations for two mounting
screws and the access hole for the Xanbus cables.
2. Using a hole saw, cut out the access hole for the Xanbus cable(s).
3. Route the Xanbus cable(s) from other Xanbus-enabled devices inside the wall and
through the access hole.
Important: To ensure communication signal
quality, the network must be terminated at
each end with a terminator.
3. Insert the mounting plate with the two tabs in a vertical
position into the hole.
4. Attach the mounting bracket with two #8
screws.
5. Connect the Xanbus cable(s) to either
network input on the back of the SCP.
Connect a network terminator to the SCP if it
is the last device at the end of a daisy chain
network layout.
7. Peel off the protective plastic coating
covering the screen and indicator light.
If network power is present, the SCP displays the Startup Screen briefly, and then
either the clock setup warning (the first time only), or the System Status screen.
Set the system clock to the correct time
Xanbus Network Layout
If the SCP is the last device on the network, the open port on the SCP must be termi-
nated.
Solar Charge
Controller
Inverter/Charger
Automatic
Generator Start
SCP
Xanbus Cable
Network Terminator
Network Terminator
Startup Screen System Status Screen
Access hole must be large
enough to easily fit the
network wire connectors
For more information about configuring the Conext system using the SCP, see the Conext
System Control Panel Owners Guide.
System Status
menu
Battery
20.4A 53.9V
AC1
115V 3202W
BatLev
E--F
Load
1235W
9:18AM Mar 10
Warning: W255
XW SCP
System clock not set.
Set correct time.
continue cancel
Clock Setup Warning
Tabs in vertical
position
Rotate tabs to horizontal
position
1. From the clock setup Warning screen, press Enter to display the Clock menu with
Set Time highlighted. Or, from the System Status screen, press Enter, highlight Clock,
and then press Enter. Press Enter again with Set Time highlighted.
2. Press Enter to select the hour value. Use the up and down arrow buttons to change the
hour, and then press Enter.
3. Repeat to set the minute value and the AM/PM value (if using the 12-hour clock).
4. Press Exit to return to the previous value, or press Exit several times to return to the
previous screen.
Note: If a Conext ComBox is installed, the ComBox network time overrides the time
settings on the SCP and other Conext devices.
AC1
AC2
Event
Equalize
kW
A
Charging
!
Inverting
Standby
Event/Warning
Conext XW SCP