User Manual

4
www.schneider-electric.com
Conext ComBox
865-1058
Copyright © 2014 Schneider Electric. All Rights Reserved.
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
ELECTRICAL SPECIFICATIONS
COMMUNICATION INTERFACES
Xanbus
Ethernet
RS 485
DATA INTERFACES
USB 2.0-Host
USB 2.0-Device
POWER SUPPLY (SELV ON ALL SOURCES)
Power Consumption
AC/DC adapter*
Xanbus
24V on RS 485 connector
MEMORY
Internal
External Micro-SD Card
GENERAL SPECIFICATIONS
Weight
Housing / Mounting System
IP rating / Mounting Location
Status Display
Temperature
Humidity
FEATURES
Programmable dry contact relay
Graphical user interface
Remote firmware upgrades
Max. number of Xanbus devices
REGULATORY
EMC immunity
EMC emission
Substances / environmental
Connector: 2 x RJ45
Products Supported: Conext XW+, SW, TX, Grid Tie,
MPPT 60, HV MPPT 80, AGS, SCP, Battery Monitor
Connector: 1 x RJ45, 10/100 MBPS, Server: FTP, Web,
Modbus TCP/IP, Client: SMTP, SNTP; Discovery: DPWS.
Modbus (1 x Connector: Screw 5-terminal, 16-24AWG,
2-wire serial, 19200 bps) Monitoring supported for:
Conext CL, RL, & TL; PM810, PM820, PM850, PM870.
USB-A, MSD protocol for firmware and device upgrades
USB-mini B, MSD protocol for exporting data logs to a PC
2 W average / 10 W peak
Input: 100-240V, 50-60Hz, 0.6A, Output: 12V, 1.5A,
5.5mm outer, 2.1mm center-positive jack
When connected to Conext XW+ / SW or HV MPPT 80
providing 15V, 200mA min or more than one Conext TX
24V, 1A max input only through pins 4 and 5
96 MB flash
2GB or more, class 2 or better recommended
250 g (0.6 lb)
ABS Plastic / DIN-rail: 35 mm, Wall-mount: 2-screw
IP 20, NEMA Type 1, Indoor only
5 x LEDS
Operating: -4 to 122 °F (-20 to 50 °C)
Storage: -40 to 185 °F (-40 to 85 °C)
Operating: < 95%, non-condensing
Storage: < 95%
Screw 3-terminal, 16-24 AWG, NC-Com-NO,
Class 2, 24V, 4A max SELV input only
Integrated Web Server for ComBox settings only (Internet
Browser), Android tablet
Yes
Up to 20 (depending on device type). See Installation and
Configuration guide for further details.
EN61000-6-1
EN61000-6-3, FCC Part 15 Class B, Ind. Canada ICES-003 Class B
RoHS
NOTE: Specifications are subject to change without notice.
DIMENSIONS
6.7 in. (169 mm)
2.1 in.
(54 mm)
4.5 in. (114 mm)
The Conext ComBox Settings page appears.
Click Settings.
Each of the Settings above, when clicked, will expand and display its sub-settings.
With some exceptions, each sub-setting is comprised of two fields – a Parameter and
its Value, and two buttons – recall (or refresh) and save.
Lost password recovery is not possible without entering a valid e-mail address
and enabling e-mail notification. To do this, click E-mail Settings.
Change only the four parameters below.
NOTE:
Change the Reset Lost Passwords to Yes, if you want a new password to be sent
to the email address in Lost Password E-Mail Recipients.
Retain the default No, if you want the actual password you had forgotten to be sent to the
email address in Lost Password E-Mail Recipients.
E-mail Settings
Mailer Status Enabled
Lost Password E-mail Recipients user@yourdomain.com
Lost Password E-mail From Address
no-reply@schneider-electric.com
Reset Lost Passwords No
Parameter Value
K Specifications
For indoor use only.
Connect the ComBox to the Xanbus network.
Illustration only. Components vary.
Do not connect a Xanbus cable plug to the 10/100 Ethernet port of the Conext ComBox.
EQUIPMENT DAMAGE
Failure to follow these instructions can damage equipment or affect network
performance.
NOTICE
NOTE:
Use Xanbus cables that are longer than 6.5 ft (2 m). The total length of all cables combined
must not exceed 131 ft (40 m).
Xanbus components can be arranged in any order. Use a network terminator at both ends of
the network. See illustration below.
Conext XW
/
SCP
AGS
Conext ComBox
Conext XW
MPPT 60 150
MPPT 60 150
Connect to Xanbus ports only.
network
terminator
network
terminator
Change the Time and Zone setting before connecting the ComBox to the Xanbus
network. To change the setting, click Time and Zone.
Time and Zone
Date/Time: 2012/12/11 12:53:18
Set Time
Set Time
Time Zone:
Set Time Zone
(-8:00) Pacific Time (US, Can
NOTE: For more information on another time-related ComBox setting called Network
Time (SNTP) and its effect on the Xanbus network, refer to the Conext ComBox Owner’s
Guide.
To change the Date/Time parameter, overwrite the existing value with the current
date (YYYY/MM/DD) and time (HH:MM:SS). Click to save the new setting.
Change all other settings as needed. Refer to the ComBox Owners Guide for
more information on all other settings.
* When ordering a replacement, reference PN: 0J-921-0023-Z.
HAZARD OF PHYSICAL INJURY AND UNEXPECTED OPERATION
Failure to follow these instructions can result in death or serious injury.
Refer to the Owner’s Guide for more detailed information when making any changes to settings
or sending commands. Commands sent to this device may affect other components in the
system. Ensure that anyone working with the system is aware of the result of your changes
before sending a command.
Be careful when changing the ComBox time setting. It will override any time settings on
individual Xanbus-enabled devices in the network. The time represents the entire system. Any
appliance or equipment that is time-controlled by a Xanbus device, such as a generator
connected to an AGS, can inadvertently turn on at the wrong time.
WARNING