Installation Guide

Configuration
3–54 975-0679-01-01 Revision F
Note: Compatibility between different firmware versions in a Master/Slave system
is not guaranteed. Therefore, ensure the same firmware version is installed on all
ComBoxes in a Master/Slave system.
Note: When there are more than 6 Conext XW’s or 10 Conext MPPT devices, it is
not recommended to use the ComBox (or SCP with cascading settings) to
configure settings on the attached Xanbus devices. Adjusting device settings
from the ComBox on such a large system can be unreliable. Use the
Conext
Configuration Tool (p/n 865-1155-01) with supplied software to configure device
settings on such large systems.