Installation Guide
Installation
2–2 975-0679-01-01 Revision F
Choosing a Location
Choose a clean, dry, easily accessible location indoors.
If you mount the Conext ComBox on a wall, the recommended height is at eye-
level so that you can clearly see the LEDs and have easy access to the data
ports.
All the communication ports on the Conext ComBox are accessible from the
bottom of the device when mounted on a wall or DIN rail. Clearance of at least 2
inches (50 mm) below the device is needed to allow for the bending radius of
cables that connect to the Conext ComBox.
You should not run cables through conduits that can be exposed to lightning
strikes. The following are recommended maximum cable lengths in a Conext
ComBox system:
131 feet (40 m) Total Xanbus network
328 feet (100 m) Router to Conext ComBox
164 feet (50 m) Modbus Master (RS 485) to Conext ComBox
DANGER
HAZARD OF ELECTRIC SHOCK AND FIRE
• Connect only to Safety Extra Low Voltage (SELV) circuits and power
sources.
• All wiring must be done by qualified personnel to ensure compliance with
all applicable installation codes and regulations.
• For Indoor Use Only.
• Do not disassemble. No user serviceable parts inside.
Failure to follow these instructions will result in death or serious injury.