Quick Start Guide

975-0718-01-01 Revision A
03-2014
3
E
Connecting the Generator
F
Connecting the AGS to the Xanbus Network
XANBUS SHOCK HAZARD
Xanbus cables in contact with DC or AC power can transmit an electric shock.
Do not route the Xanbus cables in the same conduit or panel as the AC and DC power cabling.
Failure to follow these instructions can result in death or serious injury.
WARNING
SHORT CIRCUIT OF NETWORK COMPONENTS
This network is not an ethernet system. Only connect Xanbus-enabled devices to other Xanbus-enabled devices.
Do not attempt to connect Xanbus-enabled devices to other networks or systems.
Ethernet crossover cables are not compatible with the Xanbus system. Use Category 5 (CAT 5 or CAT 5e) cables
to connect Xanbus-enabled devices.
Failure to follow these instructions can result in damage to equipment.
NOTICE
Xanbus Network Layout
The last device on the network must be terminated with a network terminator.
Solar Charge
Controller
Inverter/Charger
Xanbus Cable
Network Terminator
AC1
AC2
Event
Equalize
kW
A
Charging
!
Inverting
Standby
Event/Warning
Conext XW SCP
Automatic
Generator Start
System
Control Panel
1. Insert a Xanbus cable (standard straight-through Ethernet CAT 5e) into one of the
network ports on the bottom panel of the AGS.
2. Connect the other end of the cable to the next Xanbus-enabled device in the chain.
Depending on the layout of the Xanbus network, the following options are available for
the other Xanbus port on the AGS:
A second network cable to another device in the chain.
A network terminator (when the AGS is the last device at one end of the network).
Connect the Xanbus cables
StartStop Mode Timing Diagram for Gen Types 4, 5, 9, and 10
Relay 1: Stop
Relay 2: Start (Cranking)
Relay 3: Preheat (Glow)
& Shutdown Bypass
Start
Stop
Preheat
Delay
Crank
Time
Shutdown
Bypass
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
RUN
GENERATOR RUN SIGNAL RETURN
GENERATOR RUN SIGNAL
RUN
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse START
GENERATOR RUN SIGNAL RETURN
Type 7
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
RUN
GENERATOR RUN SIGNAL RETURN
GENERATOR RUN SIGNAL
RUN
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse START
GENERATOR RUN SIGNAL RETURN
Type 8
18
17
16
14
13
12
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP
START
GENERATOR RUN SIGNAL RETURN
Type 10
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
16
14
Relay 1
5A fuse
RUN
RELAY 1 RETURN
Type 14
RunMode Timing Diagram for Gen Types 7, 8, and 14
Relay 1: Run/Stop
(Ignition)
Relay 2: Start
(Cranking)
Relay 3: Preheat
(Glow)
Start Run Stop
Preheat
Delay
Crank
Time
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
RUN
GENERATOR RUN SIGNAL RETURN
Type 11
MomentaryRun Mode Timing Diagram for Gen Type 11
Relay 1:
Momentary Run
Relay 2: Start
(Cranking)
Relay 3: Preheat
(Glow)
Start
Run Stop
Preheat
Delay
Crank
Time
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP/PREHEAT
START
GENERATOR RUN SIGNAL RETURN
Type 13
PulseStop Mode Timing Diagram for Gen Type 13
PulseStop Mode Relay 1 Behavior
Relay 1: Stop
Relay 2: Start (Cranking)
Relay 3: Preheat (Glow)
& Shutdown Bypass
Start
Stop
Preheat
Delay
Crank
Time
Shutdown
Bypass
Relay 1: Stop
Stop
Pulse
Stop
Pulse
Stop
Pulse
Wait
Stop
WaitWait
Check
Check
Check
Harness Wires Generator Wires – User Supplied Wiring and Interconnections
www.SEsolar.com
Conext Automatic Generator Start Quick Start Guide
865-1060-02