Product Manual

Troubleshooting
5–6 975-0307-01-01
Fault Messages
When the Xantrex XW AGS detects a fault condition, it stops the
generator. The red Fault light also comes on, and the Xantrex XW System
Control Panel displays a fault message.
The Xantrex XW AGS remembers the GenMode that it was in at the time it
detected the fault. After you have cleared the fault, the Xantrex XW AGS
returns to its last known GenMode.
Table 5-26 Xantrex XW AGS Fault Messages
Fault
Number Message
Self-
clearing? Cause Action
F200 Exceeded
max number
of start tries.
Check gen,
clear fault.
No The Xantrex XW AGS
has tried and failed to
start the generator. To
prevent draining the
start battery, the
Xantrex XW AGS will
suspend further start
attempts.
Check the generator’s fuel level
and start battery condition.
Consult generator manual.
Clear fault on System Control
Panel screen to allow retry.
F201 Unable to
stop gen.
Stop gen via
its control
panel.
No The Xantrex XW AGS
has lost contact with
the generator or the
generator did not stop
after the Xantrex XW
AGS sent it a stop
signal.
Change the Xantrex XW AGS
mode to Manual Off.
If this fails to work, stop the
generator with the external
stop switch.
Check generator.
Return Xantrex XW AGS to
automatic mode to resume
automatic starts and stops.
F203 Manual Off:
Gen stopped
by ext
sensor.
Reset
GenMode.
No An external sensor
connected to the
Xantrex XW AGS has
stopped the generator
and put the Xantrex XW
AGS into Manual Off
mode.
After the sensor connected to
the external shutdown has
deactivated, clear the fault and
reset the Xantrex XW AGS to
the desired mode.