Product Manual

The Xantrex XW Automatic Generator Start Menu
975-0307-01-01 3–35
Manual Off Mode
Selecting Manual Off Mode overrides the automatic stop settings and
manually stops the generator. Manual Off must be selected to stop the
generator when the generator has been started manually. The Xantrex
XW AGS will not automatically start the generator again until “Automatic”
is selected in the GenMode Menu.
Mode
The Mode menu item is a device operating mode and provides the
means to put the Xantrex XW AGS in Standby Mode or return it from to
Operating Mode.
The Xantrex XW AGS Mode must be set to [Standby] before selecting a
generator type. Selecting Standby stops the generator (if it is running).
While in Standby, the Xantrex XW AGS “listens” to and reports its status
to the network. It will not start the generator manual or automatically while
in Standby.
The View Device Info Menu
The View Device Info menu provides a means to view the Fault, Warning
and Event logs. It is also where the settings can be restored to factory
default settings.
View Fault Log
Purpose The Fault Log displays the last 20 Xantrex XW AGS faults for reference to
assist the user in troubleshooting problems.
When to use Consult the Fault Log when troubleshooting or before seeking technical
assistance.
View Warning Log
Purpose The Warning Log displays the last 20 Xantrex XW AGS warnings for
reference.
When to use Consult the Warning Log when troubleshooting or before seeking
technical assistance.
Important: The GenMode mode must be set to Manual Off before any
start trigger settings can be changed.