Max Run Time
Full name Maximum Generator Run Time
Purpose “Max Run Time” allows a limit to be set on how long the generator will
run. This setting overrides any automatic start triggers. For example, if
the generator starts in response to low battery voltage, and the batteries
are not fully charged before “Max Run Time” is reached, the generator
will stop. In addition, when the generator is started manually from the
Xantrex XW System Control Panel, the generator will stop when “Max Run
Time” is reached.
When started with an external manual ON/OFF switch, the generator will
not stop when it reaches “Max Run Time”. The generator must be
stopped with the external manual ON/OFF switch, or by using the System
Control Panel to change the “GenMode” to ManualOff.
If the Xantrex XW AGS reaches “Max Run Time”, a warning message will
appear on the Xantrex XW System Control Panel. The Xantrex XW AGS
will stop operating until the warning is acknowledged by pressing ENTER
on the Xantrex XW System Control Panel.
Considerations Adjust the “Max Run Time” if the maximum generator run time:
exceeds the fuel capacity of the generator, or
is not long enough to fully recharge the batteries under optimum
conditions.
Values Default
0 hours to 24 hours (increments of 1hour) 8 hours