Product Manual

The Xantrex XW Automatic Generator Start Menu
975-0307-01-01 3–25
Gen Spin Down
Purpose The Gen Spin Down setting allows an interval to be set between a
generator stop signal being sent at the end of a Gen Cool Down cycle
and the Xantrex XW AGS changing the Generator State to “stopped.”
This setting is used in the Xantrex XW System to allow the generator to
completely stop, thereby reducing its output voltage to zero and pulling
the B+ signal low before the Xantrex XW Inverter/Charger can qualify
and transfer the generator.
This helps the system operate properly in cases where the generator
does not immediately stop when the stop signal is sent to the Xantrex XW
AGS. Gen Spin Down applies to all stop triggers—Stop V, Stop Load,
Stop Float, Stop Absorb, Stop Load, and Manual Off.
When to use This setting is automatically configured when a “Gen Type” is selected
for the generator. Customize the “Gen Spin Down” trigger on the advice
of the generator manufacturer or authorized service personnel.
Values Default
1s to 900s (increments of 1s) 3s