Product Manual

The Xantrex XW Automatic Generator Start Menu
975-0307-01-01 3–23
Cfg Gen Menu
The Cfg Gen Menu provides the means to customize the following
settings if the generator being used doesn’t conform to one of the preset
generator types or if an exercise period needs to be scheduled.
The Generator Configuration menu contains the following items:
“Starter Cool Down”
“Gen Cool Down”
“Gen Spin Down”
“Max Run Time”
“Exercise Per
“Exercise Dur”
“Exercise Time”
“Relay3”
“Gen Run Hold Time”
“Crank Delay”
“Crank Time”
“Crank Retry Time”
“Preheat Time”
“Gen Start Tries”
Starter Cool Down
Purpose The Starter Cool Down setting allows an interval to be set between start
attempts if the generator fails to start on the first attempt. This time period
allows the start motor to cool sufficiently before the Xantrex XW AGS
signals it to begin cranking again.
When to use This setting is automatically configured when a “Gen Type” is selected
for the generator. Customize the “Starter Cool Down” trigger on the
advice of the generator manufacturer or authorized service personnel.
Values Default
1s to 250s (increments of 1s) 60s