Product Manual
Configuration
3–22 975-0307-01-01
If “Start Load” is set too high, the Xantrex XW AGS may not start the
generator in time to recharge the batteries before the batteries are
drained by the AC load. In addition, if “Start Load” is set too high, the
inverter may shut down due to an overload condition.
If “Start Load” is set too low, the Xantrex XW AGS may start the generator
too frequently, wasting fuel in the process.
Stop Load
Full name Stop on Inverter Load Current
Purpose The “Stop Load” trigger enables the Xantrex XW AGS to stop the
generator when the AC load falls below a specific level for 1 minute. The
“Stop Load” setting applies to situations when the Xantrex XW AGS has
started the generator to assist the inverter with powering the AC load.
Dependencies The “Stop Load” trigger requires the Xantrex XW AGS to be in Automatic
mode and the “Load” trigger to be set to [Enabled]. It also needs to have
a value starting value set in the “Start Load” trigger.
Values Default
1.0 A to 28.0 A (increments of 1 A) 7.0 A