Product Manual
Installing the Xantrex XW Automatic Generator Start
975-0307-01-01 2–29
Connecting the Xantrex XW AGS to the Xantrex Xanbus Network
To connect the Xantrex XW AGS to the Xantrex Xanbus network, plug a
Xantrex Xanbus network cable (standard straight-through Ethernet
cable—CAT 5e) into one of the network ports on the bottom panel of the
Xantrex XW AGS. Connect the other end of that same cable to the next
Xantrex Xanbus-enabled component in the chain. See Figure 2-25. For the
location of the ports on the Xantrex XW AGS, see Figure 2-5 on page 2–3.
If the Xantrex XW AGS is being installed on an existing Xantrex Xanbus
system, the system must first be put into Standby. See “Putting the
Xantrex XW AGS in Standby Mode” on page 4–6.
Depending on the layout of the Xantrex Xanbus system, the following
options are available for the other network connector on the Xantrex XW
AGS:
CAUTION: Equipment Damage
Connect only to other Xantrex Xanbus-enabled devices.
Although the cabling and connectors used in this network system are the
same as those used for Ethernet, this network is not an Ethernet system.
Equipment damage may result from attempting to connect a Xantrex
Xanbus-enabled device to an Ethernet system.
Figure 2-25 Xantrex Xanbus Network Example
Solar Charge Controller
Enter Exit
Hybrid Inverter/Charger
Gri d ( AC1)
Gen ( A C2)
F aul t /
Warning
Equalize
Battery
Charging
Inverting
Flashing =s ell
Charge Controller
Xantrex XW AGS
Inverter/Charger
Xantrex XW
System Control
Panel
Network terminator
Network terminator