Product Manual
Installing the Xantrex XW Automatic Generator Start
975-0307-01-01 2–27
Connecting an External ON/OFF LED
Wires 9 (White/Blue) and 11 (Black) on the wiring harness can be
connected to an LED or other light to accompany a remote external ON/
OFF switch. This light turns on when the generator run signal is active to
visually indicate that the generator is running.
Important: With some generators, the generator run signal becomes
active during the preheat stage, before the generator is actually running.
In this case, the external ON/OFF LED (and the Generator On light on the
Xantrex XW AGS) will turn on during the preheat stage and remain on
when the generator is running.
For some generators, these lights will also remain on for a period of time
after the generator has stopped.
Figure 2-23 External ON/OFF Switch and LED Wiring Diagram
START PUSH BUTTON
STOP PUSH BUTTON
12V OR 24V
EXTERNAL LED
EXTERNAL LED
GROUND
7
8
9
10
11
13
2K
2K
5K11
Fused 12V or 24V
-12V or -24V
Generator Battery
Negative (–)
Start Push Button
Stop Push Button
External LED
External LED
XW Automatic
Generator Start
Start Push Button
Stop Push Button
External LED
Fused 12V or 24V
External LED
-12V or -24V
Ground