Product Manual
Installation
2–22 975-0307-01-01
Type 13
Type 13 is a three-wire PulseStop configuration that uses relay 3 to
provide the preheat signal. With this generator type, there will be a delay
between the generator turning off and the Xantrex XW AGS recognizing
that the generator is off.
Figure 2-21 Type 13 Connection Diagram
Table 2-17 Type 13 Relay and Timing Preset Configurations
Relay Function Preset Configuration Setting
Relay 1 mode
PulseStop
Relay 3 mode
Preheat
Gen Run signal hold time
5 s
Preheat time
15 s
Preheat to crank delay
2 s
Crank time
15 s
Crank retry time
15 s
Gen Cool Down
30 s
Gen Spin Down
3 s
Shutdown bypass time
0 s
Start tries
3